Breaker Off

Breaker Off / Wire size

Wire size for 90 amps at 300 feet

The smallest wire that carries 90 amps safely, then checked so no more than 3% of the voltage is lost over 300 feet at 240 volts.

Volts

NM-B house cable (Romex)

Not NM-B

Over 55 amps or this far, run wires in conduit or SER cable.

Copper wires in conduit (THHN)

1/0 AWG

3 AWG carries the amps; one size up keeps the drop to 2.74%

Aluminum (SER or XHHW)

3/0 AWG

2 AWG carries the amps; larger keeps the drop to 2.83%

Every size at 300 feet and 90 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A69.1%-
12 AWG20 A20 A43.4%71.5%
10 AWG30 A30 A27.2%45.0%
8 AWG40 A50 A17.2%28.4%
6 AWG55 A65 A11.0%18.2%
4 AWG70 A85 A6.93%11.4%
3 AWG85 A100 A5.51%9.07%
2 AWG95 A115 A4.37%7.18%
1 AWG110 A130 A3.46%5.69%
1/0 AWG125 A150 A2.74%4.52%
2/0 AWG145 A175 A2.18%3.58%
3/0 AWG165 A200 A1.72%2.83%
4/0 AWG195 A230 A1.37%2.25%
250 kcmil215 A255 A1.16%1.91%
300 kcmil240 A285 A0.97%1.59%
350 kcmil260 A310 A0.83%1.36%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.