Breaker Off

Breaker Off / Wire size

Wire size for 90 amps at 200 feet

The smallest wire that carries 90 amps safely, then checked so no more than 3% of the voltage is lost over 200 feet at 240 volts.

Volts

NM-B house cable (Romex)

Not NM-B

Over 55 amps or this far, run wires in conduit or SER cable.

Copper wires in conduit (THHN)

2 AWG

3 AWG carries the amps; one size up keeps the drop to 2.91%

Aluminum (SER or XHHW)

2/0 AWG

2 AWG carries the amps; larger keeps the drop to 2.38%

Every size at 200 feet and 90 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A46.0%-
12 AWG20 A20 A29.0%47.7%
10 AWG30 A30 A18.2%30.0%
8 AWG40 A50 A11.5%18.9%
6 AWG55 A65 A7.36%12.1%
4 AWG70 A85 A4.62%7.62%
3 AWG85 A100 A3.67%6.05%
2 AWG95 A115 A2.91%4.78%
1 AWG110 A130 A2.31%3.80%
1/0 AWG125 A150 A1.83%3.02%
2/0 AWG145 A175 A1.45%2.38%
3/0 AWG165 A200 A1.15%1.89%
4/0 AWG195 A230 A0.91%1.50%
250 kcmil215 A255 A0.77%1.27%
300 kcmil240 A285 A0.64%1.06%
350 kcmil260 A310 A0.55%0.91%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.