Breaker Off

Breaker Off / Wire size

Wire size for 30 amps at 300 feet

The smallest wire that carries 30 amps safely, then checked so no more than 3% of the voltage is lost over 300 feet at 240 volts.

Volts

NM-B house cable (Romex)

Not NM-B

Over 55 amps or this far, run wires in conduit or SER cable.

Copper wires in conduit (THHN)

4 AWG

10 AWG carries the amps; one size up keeps the drop to 2.31%

Aluminum (SER or XHHW)

2 AWG

8 AWG carries the amps; larger keeps the drop to 2.39%

Every size at 300 feet and 30 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A23.0%-
12 AWG20 A20 A14.5%23.9%
10 AWG30 A30 A9.08%15.0%
8 AWG40 A50 A5.73%9.45%
6 AWG55 A65 A3.68%6.06%
4 AWG70 A85 A2.31%3.81%
3 AWG85 A100 A1.84%3.02%
2 AWG95 A115 A1.46%2.39%
1 AWG110 A130 A1.16%1.90%
1/0 AWG125 A150 A0.92%1.51%
2/0 AWG145 A175 A0.73%1.19%
3/0 AWG165 A200 A0.57%0.94%
4/0 AWG195 A230 A0.46%0.75%
250 kcmil215 A255 A0.39%0.64%
300 kcmil240 A285 A0.32%0.53%
350 kcmil260 A310 A0.28%0.45%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.