Wire size for 150 amps at 300 feet
The smallest wire that carries 150 amps safely, then checked so no more than 3% of the voltage is lost over 300 feet at 240 volts.
NM-B house cable (Romex)
Not NM-B
Over 55 amps or this far, run wires in conduit or SER cable.
Copper wires in conduit (THHN)
3/0 AWG
1/0 AWG carries the amps; one size up keeps the drop to 2.87%
Aluminum (SER or XHHW)
300 kcmil
3/0 AWG carries the amps; larger keeps the drop to 2.65%
For a whole-house service only: NEC 310.12 lets a dwelling's main service or feeder run at 83% of its rating, so 150 A can use 1 AWG copper or 2/0 AWG aluminum. That does not apply to a subpanel feeder or a single circuit.
Every size at 300 feet and 150 amps
| Size | Carries, NM-B (60°C) | Carries, conduit (75°C) | Drop, copper | Drop, aluminum |
|---|---|---|---|---|
| 14 AWG | 15 A | 15 A | 115.1% | - |
| 12 AWG | 20 A | 20 A | 72.4% | 119.2% |
| 10 AWG | 30 A | 30 A | 45.4% | 75.0% |
| 8 AWG | 40 A | 50 A | 28.7% | 47.3% |
| 6 AWG | 55 A | 65 A | 18.4% | 30.3% |
| 4 AWG | 70 A | 85 A | 11.5% | 19.1% |
| 3 AWG | 85 A | 100 A | 9.19% | 15.1% |
| 2 AWG | 95 A | 115 A | 7.28% | 12.0% |
| 1 AWG | 110 A | 130 A | 5.77% | 9.49% |
| 1/0 AWG | 125 A | 150 A | 4.58% | 7.54% |
| 2/0 AWG | 145 A | 175 A | 3.63% | 5.96% |
| 3/0 AWG | 165 A | 200 A | 2.87% | 4.72% |
| 4/0 AWG | 195 A | 230 A | 2.28% | 3.75% |
| 250 kcmil | 215 A | 255 A | 1.93% | 3.18% |
| 300 kcmil | 240 A | 285 A | 1.61% | 2.65% |
| 350 kcmil | 260 A | 310 A | 1.38% | 2.27% |
How the size is picked
- Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
- Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
- Distance is one way. Measure from the panel to the load; the math counts the trip out and back.
Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.