Breaker Off

Breaker Off / Wire size

Wire size for 150 amps at 75 feet

The smallest wire that carries 150 amps safely, then checked so no more than 3% of the voltage is lost over 75 feet at 240 volts.

Volts

NM-B house cable (Romex)

Not NM-B

Over 55 amps or this far, run wires in conduit or SER cable.

Copper wires in conduit (THHN)

1/0 AWG

1.14% voltage drop

Aluminum (SER or XHHW)

3/0 AWG

1.18% voltage drop

For a whole-house service only: NEC 310.12 lets a dwelling's main service or feeder run at 83% of its rating, so 150 A can use 1 AWG copper or 2/0 AWG aluminum. That does not apply to a subpanel feeder or a single circuit.

Every size at 75 feet and 150 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A28.8%-
12 AWG20 A20 A18.1%29.8%
10 AWG30 A30 A11.3%18.8%
8 AWG40 A50 A7.16%11.8%
6 AWG55 A65 A4.60%7.58%
4 AWG70 A85 A2.89%4.76%
3 AWG85 A100 A2.30%3.78%
2 AWG95 A115 A1.82%2.99%
1 AWG110 A130 A1.44%2.37%
1/0 AWG125 A150 A1.14%1.88%
2/0 AWG145 A175 A0.91%1.49%
3/0 AWG165 A200 A0.72%1.18%
4/0 AWG195 A230 A0.57%0.94%
250 kcmil215 A255 A0.48%0.79%
300 kcmil240 A285 A0.40%0.66%
350 kcmil260 A310 A0.34%0.57%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.