Wire size for 70 amps at 300 feet

The smallest wire that carries 70 amps safely, then checked so no more than 3% of the voltage is lost over 300 feet at 240 volts.

Volts

NM-B house cable (Romex)

Not NM-B

Over 55 amps or this far, run wires in conduit or SER cable.

Copper wires in conduit (THHN)

1 AWG

4 AWG carries the amps; one size up keeps the drop to 2.69%

Aluminum (SER or XHHW)

2/0 AWG

3 AWG carries the amps; larger keeps the drop to 2.78%

Every size at 300 feet and 70 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A53.7%-
12 AWG20 A20 A33.8%55.6%
10 AWG30 A30 A21.2%35.0%
8 AWG40 A50 A13.4%22.1%
6 AWG55 A65 A8.59%14.1%
4 AWG70 A85 A5.39%8.89%
3 AWG85 A100 A4.29%7.05%
2 AWG95 A115 A3.40%5.58%
1 AWG110 A130 A2.69%4.43%
1/0 AWG125 A150 A2.13%3.52%
2/0 AWG145 A175 A1.69%2.78%
3/0 AWG165 A200 A1.34%2.21%
4/0 AWG195 A230 A1.06%1.75%
250 kcmil215 A255 A0.90%1.48%
300 kcmil240 A285 A0.75%1.24%
350 kcmil260 A310 A0.64%1.06%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.