Breaker Off

Breaker Off / Wire size

Wire size for 30 amps at 50 feet

The smallest wire that carries 30 amps safely, then checked so no more than 3% of the voltage is lost over 50 feet at 240 volts.

Volts

NM-B house cable (Romex)

10 AWG

1.51% voltage drop

Copper wires in conduit (THHN)

10 AWG

1.51% voltage drop

Aluminum (SER or XHHW)

8 AWG

1.57% voltage drop

Every size at 50 feet and 30 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A3.84%-
12 AWG20 A20 A2.41%3.97%
10 AWG30 A30 A1.51%2.50%
8 AWG40 A50 A0.95%1.57%
6 AWG55 A65 A0.61%1.01%
4 AWG70 A85 A0.39%0.64%
3 AWG85 A100 A0.31%0.50%
2 AWG95 A115 A0.24%0.40%
1 AWG110 A130 A0.19%0.32%
1/0 AWG125 A150 A0.15%0.25%
2/0 AWG145 A175 A0.12%0.20%
3/0 AWG165 A200 A0.10%0.16%
4/0 AWG195 A230 A0.08%0.13%
250 kcmil215 A255 A0.06%0.11%
300 kcmil240 A285 A0.05%0.09%
350 kcmil260 A310 A0.05%0.08%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.

Nearby answers