Breaker Off

Breaker Off / Wire size

Wire size for 100 amps at 50 feet

The smallest wire that carries 100 amps safely, then checked so no more than 3% of the voltage is lost over 50 feet at 240 volts.

Volts

NM-B house cable (Romex)

Not NM-B

Over 55 amps or this far, run wires in conduit or SER cable.

Copper wires in conduit (THHN)

3 AWG

1.02% voltage drop

Aluminum (SER or XHHW)

1 AWG

1.05% voltage drop

For a whole-house service only: NEC 310.12 lets a dwelling's main service or feeder run at 83% of its rating, so 100 A can use 4 AWG copper or 2 AWG aluminum. That does not apply to a subpanel feeder or a single circuit.

Every size at 50 feet and 100 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A12.8%-
12 AWG20 A20 A8.04%13.3%
10 AWG30 A30 A5.04%8.33%
8 AWG40 A50 A3.18%5.25%
6 AWG55 A65 A2.05%3.37%
4 AWG70 A85 A1.28%2.12%
3 AWG85 A100 A1.02%1.68%
2 AWG95 A115 A0.81%1.33%
1 AWG110 A130 A0.64%1.05%
1/0 AWG125 A150 A0.51%0.84%
2/0 AWG145 A175 A0.40%0.66%
3/0 AWG165 A200 A0.32%0.53%
4/0 AWG195 A230 A0.25%0.42%
250 kcmil215 A255 A0.21%0.35%
300 kcmil240 A285 A0.18%0.29%
350 kcmil260 A310 A0.15%0.25%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.

Nearby answers