Wire size for 50 amps at 50 feet

The smallest wire that carries 50 amps safely, then checked so no more than 3% of the voltage is lost over 50 feet at 240 volts.

Volts

NM-B house cable (Romex)

6 AWG

1.02% voltage drop

Copper wires in conduit (THHN)

8 AWG

1.59% voltage drop

Aluminum (SER or XHHW)

6 AWG

1.68% voltage drop

Every size at 50 feet and 50 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A6.40%-
12 AWG20 A20 A4.02%6.63%
10 AWG30 A30 A2.52%4.17%
8 AWG40 A50 A1.59%2.63%
6 AWG55 A65 A1.02%1.68%
4 AWG70 A85 A0.64%1.06%
3 AWG85 A100 A0.51%0.84%
2 AWG95 A115 A0.40%0.66%
1 AWG110 A130 A0.32%0.53%
1/0 AWG125 A150 A0.25%0.42%
2/0 AWG145 A175 A0.20%0.33%
3/0 AWG165 A200 A0.16%0.26%
4/0 AWG195 A230 A0.13%0.21%
250 kcmil215 A255 A0.11%0.18%
300 kcmil240 A285 A0.09%0.15%
350 kcmil260 A310 A0.08%0.13%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.