Wire size for 80 amps at 250 feet

The smallest wire that carries 80 amps safely, then checked so no more than 3% of the voltage is lost over 250 feet at 240 volts.

Volts

NM-B house cable (Romex)

Not NM-B

Over 55 amps or this far, run wires in conduit or SER cable.

Copper wires in conduit (THHN)

1 AWG

4 AWG carries the amps; one size up keeps the drop to 2.57%

Aluminum (SER or XHHW)

2/0 AWG

2 AWG carries the amps; larger keeps the drop to 2.65%

Every size at 250 feet and 80 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A51.2%-
12 AWG20 A20 A32.2%53.0%
10 AWG30 A30 A20.2%33.3%
8 AWG40 A50 A12.7%21.0%
6 AWG55 A65 A8.18%13.5%
4 AWG70 A85 A5.13%8.47%
3 AWG85 A100 A4.08%6.72%
2 AWG95 A115 A3.23%5.32%
1 AWG110 A130 A2.57%4.22%
1/0 AWG125 A150 A2.03%3.35%
2/0 AWG145 A175 A1.61%2.65%
3/0 AWG165 A200 A1.28%2.10%
4/0 AWG195 A230 A1.01%1.67%
250 kcmil215 A255 A0.86%1.41%
300 kcmil240 A285 A0.71%1.18%
350 kcmil260 A310 A0.61%1.01%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.