Wire size for 80 amps at 100 feet

The smallest wire that carries 80 amps safely, then checked so no more than 3% of the voltage is lost over 100 feet at 240 volts.

Volts

NM-B house cable (Romex)

Not NM-B

Over 55 amps or this far, run wires in conduit or SER cable.

Copper wires in conduit (THHN)

4 AWG

2.05% voltage drop

Aluminum (SER or XHHW)

2 AWG

2.13% voltage drop

Every size at 100 feet and 80 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A20.5%-
12 AWG20 A20 A12.9%21.2%
10 AWG30 A30 A8.07%13.3%
8 AWG40 A50 A5.09%8.40%
6 AWG55 A65 A3.27%5.39%
4 AWG70 A85 A2.05%3.39%
3 AWG85 A100 A1.63%2.69%
2 AWG95 A115 A1.29%2.13%
1 AWG110 A130 A1.03%1.69%
1/0 AWG125 A150 A0.81%1.34%
2/0 AWG145 A175 A0.64%1.06%
3/0 AWG165 A200 A0.51%0.84%
4/0 AWG195 A230 A0.41%0.67%
250 kcmil215 A255 A0.34%0.56%
300 kcmil240 A285 A0.29%0.47%
350 kcmil260 A310 A0.24%0.40%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.