Wire size for 40 amps at 100 feet

The smallest wire that carries 40 amps safely, then checked so no more than 3% of the voltage is lost over 100 feet at 240 volts.

Volts

NM-B house cable (Romex)

8 AWG

2.55% voltage drop

Copper wires in conduit (THHN)

8 AWG

2.55% voltage drop

Aluminum (SER or XHHW)

6 AWG

8 AWG carries the amps; larger keeps the drop to 2.69%

Every size at 100 feet and 40 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A10.2%-
12 AWG20 A20 A6.43%10.6%
10 AWG30 A30 A4.03%6.67%
8 AWG40 A50 A2.55%4.20%
6 AWG55 A65 A1.64%2.69%
4 AWG70 A85 A1.03%1.69%
3 AWG85 A100 A0.82%1.34%
2 AWG95 A115 A0.65%1.06%
1 AWG110 A130 A0.51%0.84%
1/0 AWG125 A150 A0.41%0.67%
2/0 AWG145 A175 A0.32%0.53%
3/0 AWG165 A200 A0.26%0.42%
4/0 AWG195 A230 A0.20%0.33%
250 kcmil215 A255 A0.17%0.28%
300 kcmil240 A285 A0.14%0.24%
350 kcmil260 A310 A0.12%0.20%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.