Wire size for 200 amps at 250 feet

The smallest wire that carries 200 amps safely, then checked so no more than 3% of the voltage is lost over 250 feet at 240 volts.

Volts

NM-B house cable (Romex)

Not NM-B

Over 55 amps or this far, run wires in conduit or SER cable.

Copper wires in conduit (THHN)

4/0 AWG

3/0 AWG carries the amps; one size up keeps the drop to 2.53%

Aluminum (SER or XHHW)

300 kcmil

250 kcmil carries the amps; larger keeps the drop to 2.95%

For a whole-house service only: NEC 310.12 lets a dwelling's main service or feeder run at 83% of its rating, so 200 A can use 2/0 AWG copper or 4/0 AWG aluminum. That does not apply to a subpanel feeder or a single circuit.

Every size at 250 feet and 200 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A127.9%-
12 AWG20 A20 A80.4%132.5%
10 AWG30 A30 A50.4%83.3%
8 AWG40 A50 A31.8%52.5%
6 AWG55 A65 A20.5%33.7%
4 AWG70 A85 A12.8%21.2%
3 AWG85 A100 A10.2%16.8%
2 AWG95 A115 A8.08%13.3%
1 AWG110 A130 A6.42%10.5%
1/0 AWG125 A150 A5.08%8.38%
2/0 AWG145 A175 A4.03%6.63%
3/0 AWG165 A200 A3.19%5.25%
4/0 AWG195 A230 A2.53%4.17%
250 kcmil215 A255 A2.15%3.53%
300 kcmil240 A285 A1.79%2.95%
350 kcmil260 A310 A1.53%2.52%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.